(FA-)MPYC(Y)SLA Multicore,EPR insulated PVC sheathed steel wire braided (and PVC protective covered) (flame retardent) cable with common shield  150/250V

(FA-)MPYC(Y)SLA Multicore,EPR insulated PVC sheathed steel wire braided (and PVC protective covered) (flame retardent) cable with common shield 150/250V


Applications

This product can be used for all kinds of control systems and lighting systems of marine and offshore constructions(such as oil platforms).It is also applicable to metallurgy, chemical industry, power plant and mining industry.

Overview

Construction of (FA-)MPYC(Y)SLA Multicore,EPR insulated PVC sheathed steel wire braided (and PVC protective covered) (flame retardent) cable with common shield  150/250V:

ComponentsCodeMaterial/Description
ConductorMTinned annealed copper wire, stranded
InsulationPEP rubber
Common screenSLA
Aluminium backed polyester tape with a copper drain wire
SheathYPVC
ArmorC
Galvanized steel wire braid
Paint
Paint in red on braid (for protective type, paint is dispensable)
Protective coveringYPVC
Rated Voltage
150/250V
Standards applied of (FA-)MPYC(Y)SLA Multicore,EPR insulated PVC sheathed steel wire braided (and PVC protective covered) (flame retardent) cable with common shield  150/250V:

Design:JIS C 3410

Flame Retardant:IEC 60332-1

Flame Retardant(FA type):IEC 60332-2-22

Nominal size of (FA-)MPYC(Y)SLA Multicore,EPR insulated PVC sheathed steel wire braided (and PVC protective covered) (flame retardent) cable with common shield  150/250V:

No.of
 cores
Conductor SizeOverall Diameter Approx. Weight
(FA-)MPYCSLA(FA-)MPYCYSLA(FA-)MPYCSLA(FA-)MPYCYSLA
mm² Strandingmm±mmmm±mm kg/km
21 7/0.4310.20.412.00.5160200
411.40.513.40.5210260
713.40.515.40.6290355
1217.00.719.20.8445530
1919.80.822.20.9615725
2723.60.926.21.0845985
3726.31.129.11.210701240
4429.51.232.51.312901490